4 Operation

4.8.8 Speed Limit Detection Signal (/VLT)

4-56

Internal Speed Limit Function

If the internal speed limit function is selected in Pn002.1, set the limit of the maximum speed of the servomo-
tor in Pn407. The limit of the speed in Pn408.1 can be either the maximum speed of the servomotor or the

overspeed alarm detection speed. Select the overspeed alarm detection speed to limit the speed to the maxi-

mum speed of the servomotor or the equivalent.

Note: The servomotor’s maximum speed or the overspeed alarm detection speed will be used when the setting in this

parameter exceeds the maximum speed of the servomotor used.

External Speed Limit Function

If the external speed limit function is selected in Pn002.1, the motor speed is controlled by the speed limit
value (VLIM). For details, refer to

Σ

-V Series User’s Manual, MECHATROLINK-II Commands (No: SIEP

S800000 54).

Pn407

Speed Limit During Torque Control

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 10000

1 min

-1

10000

Immediately

Setup

Torque

Parameter

Meaning

When

Enabled

Classification

Pn408

n.

0

[Factory setting]

Uses the smaller value of the maximum motor speed
and the value of Pn407 as the speed limit value.

After restart

Setup

n.

1

Uses the smaller value of the overspeed alarm detec-

tion speed and the value of Pn407 as speed limit value.