4 Operation

4.9.2 External Device Monitor (EDM1)

4-64

(1) Connection Example and Specifications of EDM1 Output Signal

Connection example and specifications of EDM1 output signal are explained below.

Connection Example

EDM1 output signal is used for source circuit.

Specifications

Electrical characteristics of EDM1 signal are as follows.

For safety function signal connections, the input signal is the 0 V common and the output
signal is the source output. This is opposite to other signals described in this manual. To
avoid confusion, the ON and OFF status of signals for safety functions are defined as fol-
lows:
ON: The state in which the relay contacts are closed or the transistor is ON and current

flows into the signal line.

OFF: The state in which the relay contacts are open or the transistor is OFF and no cur-

rent flows into the signal line.

Host controller

EDM1+

CN8

EDM1-

8

7

0 V

24-V power supply

SERVOPACK

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Output

EDM1

CN8-8
CN8-7

ON (closed)

Both the /HWBB1 and the /HWBB2 signals are working
normally.

OFF (open)

The /HWBB1 signal, the /HWBB2 signal or both are not
working normally.

Items

Characteristics

Remarks

Maximum Allowable Voltage

30 VDC

Maximum Current

50 mADC

Maximum Voltage Drop at ON

1.0 V

Voltage between EDM1+ and EDM1- when current is 50
mA

Maximum Delay Time

20 ms

Time from the change in /HWBB1 or /HWBB2 until the
change in EDM1