9.2 Warning Displays

9-25

9

Trou

blesh

ooting

A.920:

Regenerative

Overload
(Warning before
the alarm A.320
occurs)

The power supply volt-
age exceeds the speci-

fied limit.

Measure the power supply voltage.

Set the power supply voltage within
the specified range.

Insufficient external
regenerative resistance,
regenerative resistor

capacity, or SERVO-
PACK capacity.
Or, regenerative power
has been continuously
flowing back.

Check the operating condition or the
capacity using the capacity selection
Software SigmaJunmaSize+, etc.

Change the regenerative resistance,
regenerative resistor capacity, or SER-
VOPACK capacity. Reconsider the

operating conditions using the capac-
ity selection software SigmaJunma-
Size+, etc.

Regenerative power

continuously flowed
back because negative
load was continuously

applied.

Check the load to the servomotor dur-

ing operation.

Reconsider the system including servo
drives, machine, and operating condi-
tions.

A.921:

Dynamic Brake

Overload
(Warning before
the alarm A.731
occurs)

The servomotor rotates

because of external
force.

Check the operation status.

Take measures to ensure the servomo-

tor will not rotate because of external
force.

The rotating energy at a
DB stop exceeds the DB
resistance capacity.

Check the power consumed by DB
resistance (Un00B) to see how many
times the DB has been used.

Reconsider the following:

• Reduce the motor reference speed.
• Reduce the moment of inertia ratio.
• Reduce the number of times of the

DB stop operation.

A SERVOPACK fault
occurred.

The SERVOPACK may be faulty.
Replace the SERVOPACK.

A.930:

Absolute Encod-

er Battery Error
(The absolute
encoder battery
voltage is lower
than the specified
value.)
∗ Only when an

absolute encoder
is connected.

The battery connection

is incorrect.

Check the battery connection.

Reconnect the battery.

The battery voltage is

lower than the specified

value 2.7 V.

Measure the battery voltage.

Replace the battery.

A SERVOPACK fault

occurred.

The SERVOPACK may be faulty.

Replace the SERVOPACK.

A.94A
Data Setting

Warning 1
(Parameter Num-
ber Error)

Disabled parameter
number was used.

Refer to 9.3 Monitoring Communica-
tion Data on Occurrence of an Alarm
or Warning
to determine which
command was the cause of the
warning.

Use the correct parameter number.

A.94B
Data Setting

Warning 2
(Out of Range)

Attempted to send val-
ues outside the range to
the command data.

Refer to 9.3 Monitoring Communica-
tion Data on Occurrence of an Alarm
or Warning
to determine which
command was the cause of the
warning.

Set the value of the parameter within

the allowable range.

A.94C
Data Setting

Warning 3
(Calculation Er-
ror)

Calculation result of set
value is incorrect.

Refer to 9.3 Monitoring Communica-
tion Data on Occurrence of an Alarm
or Warning
to determine which
command was the cause of the
warning.

Set the value of the parameter within
the allowable range.

A.94D
Data Setting

Warning 4
(Parameter Size)

Parameter size set in
command is incorrect.

Refer to 9.3 Monitoring Communica-
tion Data on Occurrence of an Alarm
or Warning
to determine which
command was the cause of the
warning.

Use the correct parameter size.

(cont’d)

Warning Num-

ber: Warning

Name (Warning

Description)

Cause

Investigative Actions

Corrective Actions