6-12

6.6 Initializing Parameter Settings (Fn005)

This function is used when returning to the factory settings after changing parameter settings.

Note: Any value adjusted with Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.

(1) Preparation

The following conditions must be met to initialize the parameter values.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.

(2) Operating Procedure

Use the following procedure.

• Be sure to initialize the parameter settings while the servomotor power is OFF

.

• After initialization, turn OFF the power supply and then turn ON again to validate the

settings.

Step

Display after Operation

Keys

Operation

1

Press the

Key to view the main menu for the

utility function.
Use the

or

Key to move through the list and

select Fn005.

2

Press the

Key. The display changes to the Fn005

execution display.

3

Press the

Key to initialize parameters.

During initialization, "Parameter Init" is flashing in
the display.
After the initialization is completed, "Parameter Init"
stops flashing and the status display changes as fol-
lows: "BB" to "DONE" to "BB."
Note:

Press the

Key not to ini-

tialize parameters. The display returns to the
main menu of the utility function.

4

To enable the change in the setting, turn the power OFF and ON again.

B B

− F U N C T I O N −

F n 0 0 4 : P r o g r a m J O G
F n 0 0 5 : P r m I n i t
F n 0 0 6 : A l m H i s t C l r
F n 0 0 8 : M t u r n C l r

46 and
64

B B
P a r a m e t e r l n i t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]

B B
P a r a m e t e r l n i t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]