6.12 Write Prohibited Setting (Fn010)

6-21

6

Util

ity Fu

nctions (Fn

)

6.12 Write Prohibited Setting (Fn010)

This function prevents changing parameters by mistake and sets restrictions on the execution of the utility

function.

Parameter changes and execution of the utility function become restricted in the following manner when Write

prohibited (P.0001) is assigned to the write prohibited setting parameter (Fn010).

• Parameters: Cannot be changed. If you attempt to change it, "NO-OP" will flash on the display and the

screen will return to the main menu.

• Utility Function: Some functions cannot be executed. (Refer to the following table.) If you attempt to exe-

cute these utility functions, "NO-OP" will flash on the display and the screen will return to the main menu.

Parameter

No.

Function

Write Prohibited

Setting

Reference

Section

Fn000

Alarm history display

Executable

6.2

Fn002

JOG operation

Cannot be executed

6.3

Fn003

Origin search

Cannot be executed

6.4

Fn004

Program JOG operation

Cannot be executed

6.5

Fn005

Initializing parameter settings

Cannot be executed

6.6

Fn006

Clearing alarm history

Cannot be executed

6.7

Fn008

Absolute encoder multiturn reset and encoder alarm reset

Cannot be executed

4.7.4

Fn00C

Offset adjustment of analog monitor output

Cannot be executed

6.8

Fn00D

Gain adjustment of analog monitor output

Cannot be executed

6.9

Fn00E

Automatic offset-signal adjustment of the motor current detection
signal

Cannot be executed

6.10

Fn00F

Manual offset-signal adjustment of the motor current detection
signal

Cannot be executed

6.11

Fn010

Write prohibited setting

6.12

Fn011

Servomotor model display

Executable

6.13

Fn012

Software version display

Executable

6.14

Fn013

Multiturn limit value setting change when a multiturn limit dis-
agreement alarm occurs

Cannot be executed

4.7.7

Fn014

Resetting configuration error in option modules

Cannot be executed

6.15

Fn01B

Vibration detection level initialization

Cannot be executed

6.16

Fn01E

Display of SERVOPACK and servomotor ID

Executable

6.17

Fn01F

Display of servomotor ID in feedback option module

Executable

6.18

Fn020

Origin setting

Cannot be executed

6.19

Fn030

Software reset

Executable

6.20

Fn200

Tuning-less levels setting

Cannot be executed

5.2.2

Fn201

Advanced autotuning

Cannot be executed

5.3.2

Fn202

Advanced autotuning by reference

Cannot be executed

5.4.2

Fn203

One-parameter tuning

Cannot be executed

5.5.2

Fn204

Anti-resonance control adjustment function

Cannot be executed

5.6.2

Fn205

Vibration suppression function

Cannot be executed

5.7.2

Fn206

EasyFFT

Cannot be executed

6.21

Fn207

Online vibration monitor

Cannot be executed

6.22