Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - MECHATROLINK-II Communications Reference User Manual

Page 308

Advertising
background image

9.1 Alarm Displays

9-11

9

Trou

blesh

ooting

A.330:
Main Circuit Power

Supply Wiring Error
(Detected when the

power to the main circuit
is turned ON.)

The regenerative resistor discon-

nected when the SERVOPACK

power supply voltage was high.

Measure the resistance of the regen-

erative resistor using a measuring

instrument.

When using a regenerative resistor

built in the SERVOPACK:
Replace the SERVOPACK.
When using an external regenera-

tive resistor:
Replace the external regenerative

resistor.

In the AC power input mode, DC

power was supplied.

Check the power supply to see if it

is a DC power supply.

Correct the settings to match the

actual power supply specifications.

In the DC power input mode, AC

power was supplied.

Check the power supply to see if it

is an AC power supply.

Correct the settings to match the

actual power supply specifications.

Regenerative resistor capacity
(Pn600) is set to a value other
than 0 for a SGDV-R70, -R90, -

1R6, -2R1, or -2R8 SERVO-
PACK, and an external regenera-
tive resistor is not connected.

Check the external regenerative

resistor connection and the value of

the Pn600.

Connect the external regenerative

resistor, or set Pn600 to 0 if no

regenerative resistor is required.

The jumper between the power

supply terminals B2 and B3 is

removed for the SERVOPACKs

other than the SERVOPACKs

shown above.

Confirm that a jumper is mounted

between the power supply terminals

B2 and B3.

Correctly mount a jumper.

A SERVOPACK fault occurred.

The SERVOPACK may be faulty.

Replace the SERVOPACK.

A.400:
Overvoltage
(Detected in the SER-
VOPACK main circuit
power supply section.)

• For 100-VAC SERVOPACKs:

The AC power supply voltage
exceeded 145 V.

• For 200-VAC SERVOPACKs:

The AC power supply voltage
exceeded 290 V.

• For 400-VAC SERVOPACKs:

The AC power supply voltage
exceeded 580 V.

• For 200-VAC SERVOPACKs:

with DC power supply input:
The DC power supply voltage
exceeded 410 V.

• For 400-VAC SERVOPACKs:

The DC power supply voltage
exceeded 820 V.

Measure the power supply voltage.

Set AC/DC power supply voltage
within the specified range.

The power supply is unstable, or
was influenced by a lightning
surge.

Measure the power supply voltage.

Improve the power supply condi-
tions by installing a surge absorber,
etc. Then, turn the power supply
OFF and ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

Voltage for AC power supply was
too high during acceleration or
deceleration.

Check the power supply voltage and
the speed and torque during opera-
tion.

Set AC power supply voltage within
the specified range.

The external regenerative resis-
tance is too high for the actual
operating conditions.

Check the operating conditions and
the regenerative resistance.

Select a regenerative resistance

value appropriate for the operating
conditions and load.

The moment of inertia ratio
exceeded the allowable value.

Confirm that the moment of inertia
ratio is within the allowable range.

Increase the deceleration time, or
reduce the load.

A SERVOPACK fault occurred.

Turn the control power OFF and
then ON again while the main cir-
cuit power supply is OFF. If the
alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions

Advertising