4 automatic restart after mains connection/trouble, Automatic restart after mains connection/trouble, 4drive interface – Lenze 9400 User Manual

Page 104: Danger

Advertising
background image

4

Drive interface

4.4

Automatic restart after mains connection/trouble...

104

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.4

Automatic restart after mains connection/trouble...

.../Fault/"Safe torque off active"
In

C00142

, the starting performance of the controller after mains connection and reset of "Trouble",

"Fault", or "Safe torque off active" can be parameterised.

Auto-start option 0: Auto restart inhibited after mains connection
Controller inhibit always has to be set if the controller is to change from the "Ready to switch on"

state to the "Switched on" state after mains connection or reset of "Trouble", "Fault", or "Safe torque

off active". The following change to the "Operation" state is performed when the controller is

enabled:

[4-25] State change when auto-restart is inhibited (C00142 = "0: Inhibited")

Danger!

If automatic restart is enabled (

C00142

= "1: Enabled"), the drive can restart

automatically from the "Trouble" and "Safe torque off" device states when the trouble or

request for "Safe torque off active" has been eliminated!

Note!

From software version V4.0

the automatic restart is inhibited in the Lenze setting! Set

the selection "1: Enabled" in

C00142

to obtain the former behaviour.

Controller pulses are inhibited

Controller pulses are enabled


With controller inhibit after power-on

Without controller inhibit after power-on

RFR

Œ

0

1

RFR

RFR

RFR

t

t



Initialisation

Switched on

Operation

Ready to switch on

Initialisation

Switched on

Operation

Ready to switch on