Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

107

4

Drive interface

4.6

Device output power

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.6

Device output power

The parameters described in the following subchapters influence the output power of the

controller.

4.6.1

Switching frequency

The controller uses a pulse-width modulation to generate its output voltage. The switching

frequency is used to change the control factor of the pulse-width modulation.

Automatic switching frequency reduction
In the Lenze setting, the "variable" switching frequency "8 kHz" has been selected in

C00018

, which

means that the controller automatically reduces the switching frequency depending on the

setpoint current.

• Depending on the current amount, it is changed down to an assigned switching frequency.
• The switching thresholds are device-dependent (see 9400 hardware manual, chapter "Rated

data").

• If a fixed switching frequency is selected in

C00018

instead of a variable one, there is no

switching frequency changeover, however, (due to the field frequency range 0...5 Hz) it can only

be traversed at a low continuous current and low maximum currents (see 9400 hardware

manual, chapter "Rated data").

Tip!
If a load profile and a fixed setting of the switching frequency (e. g. 8 kHz fixed) are given,

an I x t disconnection due to a high device utilisation can be avoided by selecting the

variable setting for the same switching frequency instead.

Monitoring of the device

utilisation

Note!

If parameterisation is carried out offline or if the memory module is exchanged between

different 9400 HighLine device types, always check the setting of the switching

frequency in

C00018

and adapt it, if required, to prevent a parameter error after the

parameter set download or module change!
The maximum output frequency of the controller is limited to 1/8 of the switching

frequency selected in

C00018

! (See the following table.)

Switching frequency (

C00018

):

1 kHz

2 kHz

4 kHz

8 kHz

16 kHz

Maximum output frequency:

125 Hz

250 Hz

500 Hz

1000 Hz

1999 Hz

Motor - number of pole pairs:

Maximum speed [rpm]

1

7500

15000

30000

60000

120000

2

3750

7500

15000

30000

60000

3

2500

5000

10000

20000

40000

4

1875

3750

7500

15000

30000

5

1500

3000

6000

12000

24000

6

1250

2500

5000

10000

20000