5

Motor interface

5.9

Monitoring

230

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.9.5

Maximum current monitoring

The ultimate motor current I

ULT

to be parameterised in

C00620

is a limit value to protect the motor

from destruction or influence of the rated data.

• This limit value must not be travelled cyclically in the drive process.
• The maximum current parameterisable in

C00022

should have a sufficient distance from this

limit value.

• If the instantaneous value of the motor current exceeds the limit value set in

C00620

the

response set in

C00619

is executed for motor protection (Lenze setting: Fault).

Note!

When you select a Lenze motor from the catalogue and transfer the plant parameters of

the motor to the controller, the setting in

C00620

is automatically adjusted to the

selected motor.