1 use of an external position encoder, Use of an external position encoder, Use of an external position encoder ( 239) – Lenze 9400 User Manual

Page 239: 6encoder evaluation

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

239

6

Encoder evaluation

6.1

Internal interfaces | "LS_Feedback" system block

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.1.1

Use of an external position encoder

The FDB_dnActPosIn_p input serves to evaluate an external encoder (CAN, SSI, Profibus) for the

position control.

• Via this input, a current actual position of an external encoder in [increments] can be directly

transferred to the encoder evaluation.

How to activate the use of the external actual position:
On the Application parameters

tab in the dialog level Overview Drive interface Machine parameters:

1. Select the "Position controller active" setting in the Position control structure list field

(

C02570

), so that the position encoder is evaluated.

2. Set "From application" in the Position encoder selection list field (

C00490

).

Note!

• Encoder inversion and offset selection FDB_dnPositionOffset_p also affect the

external actual position.

• If the use of the external actual position preset via FDB_dnActPosIn_p is activated, the

"Home position known" status (HM_bHomePosAvailable = TRUE) is automatically set

and homing with the basic function "Homing" cannot be activated anymore.

• If the traversing range (

C02528

) is set to "Modulo", the external actual position also

has to be defined as modulo (0 … cycle-1).