I/O terminals

8.5

Digital outputs

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.5

Digital outputs

The controller is provided with four freely configurable digital outputs.

8.5.1

Terminal assignment/electrical data

8.5.2

Parameter setting

Short overview of parameters for the digital outputs:

Note!

Initialisation behaviour:

• After mains switching until the application is started, the digital outputs remain on

FALSE.

Exception handling:

• In the case of a critical exception within the application (e. g. reset), the digital outputs

are set to FALSE, taking the terminal polarity parameterised in

C00118

into

consideration.

Terminal

Use

Electrical data

X4/DO1

...

X4/DO4

Digital output 1 ... 4

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

Output current: Max. 50 mA per output (external

resistance > 480 Ω at 24 V)

Conversion rate: 1 kHz

X4/24O

External 24 V voltage supply for the digital outputs

X4/GO

Reference potential (digital ground)

GO

24O

DO1

DO2

DO3

DO4

X4

Parameter

Info

C00118

Digital output x - terminal pol.

C00444

Status: Digital outputs

C02802

Status word: Digital outputs

Greyed out = display parameter