3 parameter data telegram examples, 1 reading parameters, Parameter data telegram examples – Lenze 9400 User Manual

Page 322: 9"can on board" system bus

Advertising
background image

9

"CAN on board" system bus

9.7

Parameter data transfer

322

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.7.3

Parameter data telegram examples

9.7.3.1

Reading parameters

Task: The heatsink temperature of 43 °C (code

C00061

, data format INTEGER32, scaling factor 1) is

to be read from the controller with node address 5.

Telegram to drive

Response message from drive (if data have been correctly transmitted)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0605

0x40

0xC2

0x5F

0x00

0x00

0x00

0x00

0x00

Explanations on the telegram to the drive
Identifier

= 1536 + node address = 1536 + 5 = 1541 = 0x0605

(1536 = SDO1 basic identifier to the controller)

Command

= 0x40 = "Read request" (request to read a parameter from the controller)

Index

= 24575 - code number = 24575 - 61 = 24514 = 0x5FC2

Subindex

= 0 (code

C00061

does not have any subcodes)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0585

0x43

0xC2

0x5F

0x00

0x2B

0x00

0x00

0x00

Explanations on the telegram from the drive
Identifier

= 1408 + node address = 1408 + 5 = 1413 = 0x0585

(1408 = SDO1 basic identifier from the controller)

Command

= 0x43 = "Read Response" (response to read request with current value)

Index

as in telegram to the drive

Subindex
Data 1 ... 4

= 0x0000002B = 43 [°C]