2 writing parameters, 9"can on board" system bus – Lenze 9400 User Manual

Page 323

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

323

9

"CAN on board" system bus

9.7

Parameter data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.7.3.2

Writing parameters

Task: The rated current of the connected motor with I

rated

= 10.2 A (code

C00088

) is to be entered in

the controller.

Telegram to drive

Response message from drive (if data have been correctly transmitted)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0602

0x23

0xA7

0x5F

0x00

0x66

0x00

0x00

0x00

Explanations on the telegram to the drive
Identifier

= 1536 + node address = 1536 + 2 = 1538 = 0x0602

(1536 = SDO1 basic identifier to the controller)

Command

= 0x23 = "Write request" (request to write a parameter to the controller)

Index

= 24575 - code number = 24575 - 88 = 24487 = 0x5FA7

Subindex

= 0 (code

C00088

does not have any subcodes)

Data 1 ... 4

= 10,2 x 10 = 102 = 0x00000066

(Value for motor current, data type U32; display factor 1/10)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x0582

0x60

0xA7

0x5F

0x00

0x00

0x00

0x00

0x00

Explanations on the telegram from the drive
Identifier

= 1408 + node address = 1408 + 2 = 1410 = 0x0582

(1408 = SDO1 basic identifier from the controller)

Command

= 0x60 = "Write response" (acknowledgement of the write access from the controller)

Index

as in telegram to the drive

Subindex