Mode 1023: ds402 homing method 23, 11 basic drive functions – Lenze 9400 User Manual

Page 462

Advertising
background image

11

Basic drive functions

11.6

Homing

462

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Mode 1023: DS402 homing method 23

Procedures:

Case 1:

Axis does not activate the reference switch while moving towards the limit switch:

1. Movement in positive direction with profile data set 1.
2. Reversing to positive travel range limit switch.
3. Positive edge of the reference switch activates profile data set 2.
4. The following negative edge of the reference switch sets the reference.
5. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

Case 2:

Axis first activates the reference switch while moving towards the limit switch:

1. Movement in positive direction with profile data set 1.
2. Reversing with positive edge of the reference switch and change to profile data set 2.
3. The following negative edge of the reference switch sets the reference.
4. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

Case 3:

Axis already stands on the reference switch:

1. Movement in negative direction with profile data set 2.
2. The following negative edge of the reference switch sets the reference.
3. Absolute positioning to target position (

C02643

) with profile data set 2 (if

C02641

= "0").

 Reference switch

 Positive travel range limit switch

1

3

2

0

1