7 limited increment for manual jog, 11 basic drive functions – Lenze 9400 User Manual

Page 516

Advertising
background image

11

Basic drive functions

11.11

Limiter

516

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Priorisation of the limited speeds

The following applies to software versions lower than V3.0:

• If several limited speeds are requested at the same time, the parameters of the limited speed

with the lowest number are used, i.e. the "Limited speed 1" has the highest priority.

The following applies from software version V3.0:

• If several limited speeds are requested at the same time, the lowest speed with the greatest

deceleration and the lowest S-ramp time is approached from the parameters of the requested

limited speeds.

11.11.2.7 Limited increment for manual jog

Via

C02713

the maximum permissible distance (limited increment) for the basic function "

Manual

jog

" can be set.

• The request "Limited increment" is effected via the input LIM_dwControl, generally by the

control word of the safety module. If no safety module is available, the control word for the

input LIM_dwControl can also be generated by means of an inverter.

• In

C02714

the maximum permissible distance in [increments] is displayed.