63

4

Drive interface

4.2

Device commands

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.18

Activate quick stop

The

C00002

= "45: Activate quick stop" device command is used to activate the basic function

"Quick stop", i. e. the drive is brought to standstill within the deceleration time set, irrespective of

the setpoint defined.

• Quick stop can also be activated by other sources, e.g. by the application.

C00159

displays a bit code of active sources/causes for the quick stop.

Tip!
In contrast to the "stop" function, quick stop is required for a stop in the event of an error.

Thus, quick stop can also be set as an error response ("quick stop by trouble) for many

monitoring functions. Detailed information on this can be found in the chapter

"

Diagnostics & fault analysis

".

( 598)

Related device commands

Reset quick stop

( 64)

Note!

The activation of quick stop may cause following errors in superimposed controls (e.g.

synchronous or position control). If several drives execute a coordinated movement, the

quick stop function should therefore only be used for the motion master (master drive)

in order to maintain the coordination.
This device command has no status display in

C00003

, i.e. the display remains

unchanged showing the previous device command status.