Runtime error [0x006a000d, Application has stopped [0x006a000e, Breakpoint reached [0x006a000f – Lenze 9400 User Manual

Page 637: Faulty application parameter [0x006a0010, Division by zero [0x006a0011, 0x006a000e, 0x006a000f, 0x006a0011, 0x006a0010, 0x006a000d

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

637

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Runtime error [0x006a000d]

Application has stopped [0x006a000e]

Breakpoint reached [0x006a000f]

Faulty application parameter [0x006a0010]

Division by zero [0x006a0011]

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

13

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A runtime error has occurred in the application. The

application processing has been interrupted.

Remove runtime error in the application and retransfer

application to controller.

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

14

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The application has been stopped using the device

command

C00002

="32". All user tasks are stopped.

Restart application with device command

C00002

="31".

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

15

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The application has reached a set breakpoint and the

user task with the breakpoint has stopped.

Delete breakpoint and restart application.

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

16

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid parameter description is available.

Transmit application and parameter set to the controller

again.

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

17

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An impermissible division by zero occurred in the

application. The division has been intercepted and the

divisor was replaced by the value "1".

Replace application.