Controller enabled [0x00750001]

Controller in STO state [0x00750003]

Controller: Pulse inhibit is active [0x00750005]

PLC configuration invalid [0x00750006]

Heatsink: Temperature > C00122 [0x00770000]

Module ID (decimal)

Error ID (decimal)

117: Device control

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The controller is enabled and has the "Operation" state. - (Information only)

Module ID (decimal)

Error ID (decimal)

117: Device control

3

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The controller has received the "Safe torque off (STO)"

request by the safety module and is now in the "Safe

torque off active" device state.

- (Information only)

Module ID (decimal)

Error ID (decimal)

117: Device control

5

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The pulse inhibit is active in the controller.

- (Information only)

Module ID (decimal)

Error ID (decimal)

117: Device control

6

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid control configuration has occurred.

Load a different application.

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

0

Response (Lenze setting printed in bold)

Setting:

C00582

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Heatsink temperature higher than variable temperature

limit (

C00122

).

• Ambient controller temperature too high.

• Dirty fan or ventilation slots.

• Value set under C00122 is too low.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

• Set a higher value in

C00122

.