Cpu: thermal detector is defect [0x0077000e, Motor: ptc has triggered [0x0077000f, Heatsink: fan is defect [0x00770010 – Lenze 9400 User Manual

Page 644: 0x0077000e, 0x0077000d, 0x00770010, 0x0077000f, 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

644

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DC-bus capacitor: Thermal detector is defect [0x0077000d]

CPU: Thermal detector is defect [0x0077000e]

Motor: PTC has triggered [0x0077000f]

Heatsink: Fan is defect [0x00770010]

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

13

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for capacitor temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

14

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for CPU temperature supplies undefined values. Check control cabinet temperature, maybe it is too low.

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

15

Response (Lenze setting printed in bold)

Setting:

C00585

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The motor temperature detected via the terminals T1/T2

is too high.

• Motor is too hot due to an increased effective current

that results from operation with too high/too

frequent acceleration processes.

• Motor too hot due to increased ambient conditions.

• Motor too hot due to lacking cooling in the case of

self-ventilation and continuous operation with

speeds lower than the rated speed.

• Terminals T1/T2 are not assigned.

• Open circuit of the supply cables for terminals T1/T2.

• Check drive dimensioning.

• Connect PTC or thermal contact to terminals T1/T2.

• If a motor without integrated temperature

monitoring is used, switch off the monitoring

function (

C00585

="0").

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

16

Response (Lenze setting printed in bold)

Setting:

C00610

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Speed of heatsink fan too low, e.g. due to dirt.

Check/clean fan.