Can on board: bus off [0x00830000, Can on board: invalid node address 0 [0x00830001, 0x00830002 – Lenze 9400 User Manual

Page 665: 0x00830000, 0x00830001, 0x007f0004, 13 diagnostics & fault analysis

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

665

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Communication with module in MXI2 interrupted [0x007f0004]

CAN on board: Bus off [0x00830000]

CAN on board: Invalid node address 0 [0x00830001]

CAN on board: Basic configuration invalid [0x00830002]

Module ID (decimal)

Error ID (decimal)

127: Interface to the intelligent communication module

4

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication between the controller and the

extension module in module slot MXI2 cannot be

established.

• Switch off controller, plug module correctly in module

slot MXI2, switch on controller again.

• If the problem occurs again, replace the module.

Module ID (decimal)

Error ID (decimal)

131: "CAN on board": CAN dispatcher

0

Response (Lenze setting printed in bold)

Setting:

C00595

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: "Bus-Off" state

• Received too many faulty telegrams.

• Defective cable (e.g. loose contact).

• Two nodes with the same ID.

• Remove fault (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different IDs to nodes.

Module ID (decimal)

Error ID (decimal)

131: "CAN on board": CAN dispatcher

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: initialisation error

• The hardware allocation of the node address was

selected via DIP switches, and the DIP switches of the

node address are all on zero.

Note: Instead of the impermissible node address 0, node

address 1 is used.

• Set a non-zero node address by means of the DIP

switches and then switch mains.

• Activation of the software allocation of the node

number by switching over DIP switch 2, then switch

mains.

Module ID (decimal)

Error ID (decimal)

131: "CAN on board": CAN dispatcher

2

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: configuration error

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.