Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

671

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

File ProjectSelection.dat invalid [0x008c0006]

File ProjectList.dat invalid [0x008c0007]

File DeviceCFG.dat invalid [0x008c0008]

Project is not loaded [0x008c0009]

Project is not available [0x008c000a]

Module ID (decimal)

Error ID (decimal)

140: Application project manager

6

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

Reformat memory module (

C00002

="1030") and repeat

project download.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

7

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

Reformat memory module (

C00002

="1030") and repeat

project download.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

8

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

Reformat memory module (

C00002

="1030") and repeat

project download.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

9

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Application could not be loaded because of a file error.

Load new or different application.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

10

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Application not available.

• Download application with Engineer

• Switch off controller and use a different memory

module with an existing application.