Can module (mxi1): lifeguarding error [0x009e0020, 0x009d0002, 0x009e0000 – Lenze 9400 User Manual

Page 685: 0x009e0020, 13 diagnostics & fault analysis

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

685

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN module (MXI1): Basic configuration invalid [0x009d0002]

CAN module (MXI1): Heartbeat error index 1 ... 32 [0x009e0000 ... 0x009e001f]

CAN module (MXI1): Lifeguarding error [0x009e0020]

Module ID (decimal)

Error ID (decimal)

157: CAN module in MXI1: CAN dispatcher

2

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1:

Configuration error

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

158: CAN module in MXI1: CAN-NMT handler

0 ... 31

Response (Lenze setting printed in bold)

Setting:

C13613/1...32

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Cyclic node

monitoring

• Node station has not received a heartbeat telegram

from node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the controller (

C00002

="11000") or CAN reset node.

• Select a different heartbeat producer monitoring

time or switch off monitoring and reset locked error

status, if necessary.

Tip: Save the current parameter set before mains

switching and restart of the controller (

C00002

="11").

Module ID (decimal)

Error ID (decimal)

158: CAN module in MXI1: CAN-NMT handler

32

Response (Lenze setting printed in bold)

Setting:

C13614

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Cyclic node

monitoring

• Slave response: Maximum time between two node

guarding telegrams (remote transmission request

telegram) from the master has been exceeded.

Select a different Lifeguarding monitoring time or switch

off monitoring.