0x009f0000, 0x009e0021, 0x00a00000 – Lenze 9400 User Manual

Page 686: 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

686

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN module (MXI1): Faulty NMT slave configuration [0x009e0021]

CAN module (MXI1): Faulty emergency configuration [0x009f0000]

CAN module (MXI1): Node guarding error 1 ... 32 [0x00a00000 ... 0x00a0001f]

Module ID (decimal)

Error ID (decimal)

158: CAN module in MXI1: CAN-NMT handler

33

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: A

configuration error has occurred in the network

management of the CAN slave.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

159: CAN module in MXI1: CAN emergency handler

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN

emergency configuration is faulty.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN emergency settings according to

DS301V402 in the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

160: CAN module in MXI1: CAN-NMT master

0 ... 31

Response (Lenze setting printed in bold)

Setting:

C13612/1...32

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Cyclic node

monitoring

• CAN master has not received a response to a node

guarding telegram (remote transmission request

telegram) from node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the controller (

C00002

="11000") or CAN reset node.

• Select a different node guarding monitoring time or

switch off monitoring.

• Reset potentially caught error status.

Tip: Save the current parameter set before mains

switching and restart of the controller (

C00002

="11").