14.2

Parameter list | C00173

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00173

Parameter | Name:

C00173 | Mains voltage

Data type: UNSIGNED_8

Index: 24402

d

= 5F52

h

Adjustment of the DC bus voltage thresholds

• Check during commissioning and adapt, if necessary.

• All drive components connected via the DC bus must have the same thresholds.

• For selection 0 ... 3, the undervoltage threshold is firmly defined depending on the device type (see "Rated data"

chapter in the Hardware Manual).

Note: Altering this setting also has an impact on the permissible device utilisation!

In the chapter "Rated data" of the hardware manual the device types and their permissible device utilisation at a

certain mains voltage and switching frequency are specified.
Selection list

(Lenze setting printed in bold)

Info

0 230 V

Operation on 230 V mains

• Threshold for "Undervoltage on" = 200 V

• Threshold for "Undervoltage off" = 225 V

• Overvoltage threshold = 400 V

• Brake chopper threshold = 390 V

1 400/415 V

Operation on 400 V mains/415 V mains

• Threshold for "Undervoltage on" = 285 V (BF1 to BF7)

• Threshold for "Undervoltage on" = 400 V (BF8 to BF10)

• Threshold for "Undervoltage off" = 430 V

• Overvoltage threshold = 800 V

• Brake chopper threshold = 725 V

2 460/480 V

Operation on 460 V mains/480 V mains

• Threshold for "Undervoltage on" = 490 V

• Threshold for "Undervoltage off" = 535 V

• Overvoltage threshold = 800 V

• Brake chopper threshold = 765 V

3 500 V

Operation on 500 V mains

• Threshold for "Undervoltage on" = 540 V

• Threshold for "Undervoltage off" = 585 V

• Overvoltage threshold = 800 V

• Brake chopper threshold = 790 V

4 230 V, LU configurable

Operation on 230 V mains

• Undervoltage threshold is defined in

C00174

.

• Overvoltage threshold = 400 V

• Brake chopper threshold = 390 V

5 400/415 V, LU configurable

Operation on 400 V mains/415 V mains

• Undervoltage threshold is defined in

C00174

.

• Overvoltage threshold = 800 V

• Brake chopper threshold = 725 V

6 460/480 V, LU configurable

Operation on 460 V mains/480 V mains

• Undervoltage threshold is defined in

C00174

.

• Overvoltage threshold = 800 V

• Brake chopper threshold = 765 V

7 500 V, LU configurable

Operation on 500 V mains

• Undervoltage threshold is defined in

C00174

.

• Overvoltage threshold = 800 V

• Brake chopper threshold = 790 V

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1