C00376 | can sdo client tx identifier, C00377 | can sdo server node address, C00378 | can delay boot-up - operational – Lenze 9400 User Manual

Page 779: C00378, 14 parameter reference

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

779

14

Parameter reference

14.2

Parameter list | C00376

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00376

C00377

C00378

Parameter | Name:

C00376 | CAN SDO client Tx identifier

Data type: BITFIELD_32

Index: 24199

d

= 5E87

h

Identifier with which the assigned SDO client is able to transmit.

• If bit 31 is set (0x8nnnnnnn), the corresponding SDO client channel is deactivated (see DS301 V4.02).

• The client channels need not be parameterised right now. Their functionality will only be required when using

the gateway services.

"CAN on board" system bus

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Info

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: SDO invalid

... ...

Bit 31 SDO invalid

Subcodes

Lenze setting

Info

C00376/1

0x80000000

SDO client channel 1 TX ... 10 TX

C00376/...
C00376/10

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00377 | CAN SDO server node address

Data type: UNSIGNED_8

Index: 24198

d

= 5E86

h

Node address of the server with which the SDO client communicates via the selected client channel.

• The client functionality need not be activated.

• The entry is required so that the CAN-SDO client channel can be activated (see DS301 V4.02).

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

1

127

Subcodes

Lenze setting

Info

C00377/1

1

Remote server node address for SDO client channel 1 ...

10

C00377/...
C00377/10

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00378 | CAN delay boot-up - Operational

Data type: UNSIGNED_16

Index: 24197

d

= 5E85

h

Time that has to elapse after mains switching before the CAN NMT master places the "Start Remote Node" telegram

to the bus.

• This time is only used if the master bit is activated (

C00352

) and after mains switching.

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 3000 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1