C00385 | can heartbeat consumer time, C00386 | can node guarding, C00386/1 – Lenze 9400 User Manual

Page 781: Guarding in, C00386, C00385/1, C00385, 14 parameter reference

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

781

14

Parameter reference

14.2

Parameter list | C00385

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00385

C00386

Parameter | Name:

C00385 | CAN Heartbeat Consumer Time

Data type: BITFIELD_32

Index: 24190

d

= 5E7E

h

The 32 subcodes represent the nodes to be monitored by means of heartbeat.

• Each subcode entry contains the expected "heartbeat" time and the node ID (node address) from which the

heartbeat telegram is expected in the form of a bit code.

• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater value than the

heartbeat producer time of the node to be monitored.

• The response to a missing heartbeat telegram can be parameterised in

C00613

.

• Mapping of the CANopen object

I-1016

(see DS301 V4.02).

"CAN on board" system bus: heartbeat protocol

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Info

Bit 0 Heartbeat time bit 0

• Bit 0 ... 15: Heartbeat time

• Bit 16 ... 23: Node address

• Bit 24 ... 31: Reserved

... ...

Bit 31 Reserved

Subcodes

Lenze setting

Info

C00385/1

0x00000000

Monitoring entry 1 ... 32

C00385/...
C00385/32

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00386 | CAN Node Guarding

Data type: BITFIELD_32

Index: 24189

d

= 5E7D

h

The 32 subcodes represent the nodes to be monitored by the master by means of node guarding.

• Each subcode entry contains the guard time, the lifetime factor and the node ID (node address) from which the

heartbeat telegram is expected in the form of a bit code.

• The response to a missing node guarding response can be parameterised in

C00612

.

"CAN on board" system bus: node guarding protocol

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Info

Bit 0 Guard time bit 0

• Bit 0 ... 15: Guard time

• Bit 16 ... 23: Node address

• Bit 24 ... 31: Lifetime factor

... ...

Bit 31 Lifetime factor bit 7

Subcodes

Lenze setting

Info

C00386/1

0x00000000

Monitoring entry 1 ... 32

C00386/...
C00386/32

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Advertising
This manual is related to the following products: