C01191 | spec. charact.: temperature, C01192 | spec. characteristic: resistance, C01193 | motor temp. feedback system – Lenze 9400 User Manual

Page 836: C01194 | motor operating temperature, C01191/1, C01191/2, C01192/1, C01192/2, C01191, C01192

Advertising
background image

14

Parameter reference

14.2

Parameter list | C01191

836

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01191

C01192

C01193

C01194

Parameter | Name:

C01191 | Spec. charact.: temperature

Data type: UNSIGNED_32

Index: 23384

d

= 5B58

h

The special thermal sensor characteristic is selected by setting

C01190

="1"

Motor temperature monitoring

Setting range

(min. value | unit | max. value)

0

°C

255

Subcodes

Lenze setting

Info

C01191/1

25 °C

Value 1 for spec. thermal sensor characteristic

C01191/2

150 °C

Value 2 for spec. thermal sensor characteristic

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01192 | Spec. characteristic: resistance

Data type: UNSIGNED_32

Index: 23383

d

= 5B57

h

The special thermal sensor characteristic is selected by setting

C01190

="1"

Motor temperature monitoring

Setting range

(min. value | unit | max. value)

0

Ohm

30000

Subcodes

Lenze setting

Info

C01192/1

1000 Ohm

Value 1 for spec. thermal sensor characteristic

C01192/2

2225 Ohm

Value 2 for spec. thermal sensor characteristic

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01193 | Motor temp. feedback system

Data type: UNSIGNED_16

Index: 23382

d

= 5B56

h

Selection of feedback system for motor temperature detection.

Motor temperature monitoring

Selection list

(Lenze setting printed in bold)

0 Speed feedback
1 X7 (Input Resolver)
2 X8 (Input Encoder)
3 Reserved
4 Reserved
5 X7 and X8 parallel

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01194 | Motor operating temperature

Data type: INTEGER_32

Index: 23381

d

= 5B55

h

Setting range

(min. value | unit | max. value)

Lenze setting

1

°C

200 140 °C

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1