Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

891

14

Parameter reference

14.2

Parameter list | C02765

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02765

C02770

C02771

Parameter | Name:

C02765 | Enc_bError

Data type: UNSIGNED_32

Index: 21810

d

= 5532

h

From software version V7.0

Encoder evaluation:

Provision of the encoder signal of input X8

Selection list

(read only)

0 FALSE
1 TRUE

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C02770 | Operating mode

Data type: UNSIGNED_32

Index: 21805

d

= 552D

h

From software version V7.0

Basic function "

Manual jog open loop

"

Selection list

(Lenze setting printed in bold)

0 Deactivate
1 Activate

Subcodes

Lenze setting

Info

C02770/1

0: Deactivate

EnableManualMode

C02770/2

0: Deactivate

JogPositive

C02770/3

0: Deactivate

JogNegative

C02770/4

0: Deactivate

SelectTab1

C02770/5

0: Deactivate

SelectTab2

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C02771 | Frequency

Data type: INTEGER_32

Index: 21804

d

= 552C

h

From software version V7.0

Basic function "

Manual jog open loop

"

Setting range

(min. value | unit | max. value)

0.0

Hz

1000.0

Subcodes

Lenze setting

Info

C02771/1

1.0 Hz

Frequency 1

C02771/2

1.0 Hz

Frequency 2

C02771/3

1.0 Hz

Frequency 3

C02771/4

1.0 Hz

Frequency 4

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10