6. System setting

------------------------------------------------------------------------------------------------

----------------------------------------------------------------------------------------

6 - 73

check the abnormality of abrasion quantity.

„ Electrode exchange abrasion quantity (mm) : In case that the electrode's abrasion

quantity detected with the gun search exceeds the electrode exchange abrasion

quantity, it displays the warning message such as "W0105 Total electrode exceeded

exchange maximum abrasion quantity" and informs the exchange of electrode by

outputting the electrode abrasion warning signal. In case of being set to 0mm, it

doesn't check the abnormality of abrasion quantity.

„ Gun arm bending offset quantity (mm) : To originate the pressurization force, the

fixed electrode bending of a certain extent occurs. Like this, the bending of gun

to generate the pressurization force is called to the gun arm bending offset quantity.

In case of replaying the spot welding function, it pressurizes the position of movable

and fixed electrode after compensating as the quantity of offset.

„ Gun arm bending quantity/100Kgf (mm) : It sets the bending quantity of gun arm by

the pressurization force to the bending quantity per 100kgf. In case of replaying

the spot welding function, it pressurizes the position of fixed electrode after

calculating and compensating the gun arm bending quantity through this set point

and the instruction pressurization force. The bending quantity of movable electrode

doesn't be compensated.

„ Fixed electrode/Total bending (%) : In case that both fixed electrode and movable

electrode bend when pressurizing, it sets the ratio of the bending quantity of fixed

electrode per total bending.

„ Pressurization force accuracy (%) : When checking the pressurization accord, if the

practical pressurization force reaches in the range of pressurization force accuracy

comparing with the instruction pressurization force, it is recognized to the

pressurization accord. In case of being set to 0, it doesn't check the pressurization

accord.

„ Pressurization force error detection delay time (sec) : It sets the time when requires

from the start of pressurization motions to the pressurization accord. In case of

being in pressurization accord within this time, it immediately outputs the signal

of sending an electric current at the moment of pressurization accord. If it is in

pressurization accord within this time, it stops after outputting the error message

such as "E1314 It exceeded the checking time of pressurization force accord". and

if it is set to 0.0 second, it outputs the signal that is sending an electric current

without checking the pressurization force accord.

„ Maximum movable electrode abrasion quantity (mm) : In case that the abrasion quantity

of movable electrode detected with the gun search exceeds this set point, it stops