1. Safety, Operation Panel, Teach Pendant (1) Safety

------------------------------------------------------------------------------------------------

--------------------------------------------------------------------------------

1 - 13

- Connect Grounding line into the grounding bus-bar inside the controller.

- In case of direct grounding of the robot by anchoring at floor, two point

grounding both by robot manipulator and by controller can produce closed circuit

and further cause abnormal operation of the robot on the contrary. In this

case, connect the grounding line to the base of robot manipulator and disconnect

to the controller. When robot trembles during stopping operation, check and

examine the grounding status immediately since the possible main causes are

incomplete grounding or closed circuit.

- In using built-in transformer gun, primary power cable can be easily worn out

by directly contacting with the gun. In this case, connect the grounding line

to the base of robot directly and disconnect to controller in order to protect

controller and preventing from any electric shock.