Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

195

5

Motor interface

5.6

V/f control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.6.2.5

Optimise pull-out slip limitation

[5-19] Speed/torque curve of the asynchronous motor with two field weakening ranges  and 

The operating range of an asynchronous motor consists of the voltage control range  and the field

weakening range. The field weakening range again is divided into two ranges:

• In the first range , the power can be kept constant without causing motor stalling.
• The second field weakening range  is characterised by the fact that the maximum permissible

stator current (defined via

C00022

"Maximum current") is reduced to prevent motor stalling.

The override point (n

2

, M

2

) can be influenced via

C00980

("VFC: Override point of field weakening").

If the motor stalls in the field weakening range, the override point (n

2

, M

2

) can be adjusted by

decreasing

C00980

so that motor stalling is avoided.

If the motor does not provide sufficient torque in the field weakening range,

C00980

must be

increased.

0

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.1

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

2.1

2.2

2.3

2.4

2.5

2.6

2.7

2.8

2.9

3.0

3.1

3.2

3.3

3.4

n1

M = M2 * n2 /n

2

2

M2

n2

M = Mmax

M = Mmax * n1/n

0

1

2