2 monitoring, 1 overcurrent protection, Monitoring – Lenze 9400 User Manual

Page 268: Overcurrent protection, 7braking operation

Advertising
background image

7

Braking operation

7.2

Monitoring

268

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.2

Monitoring

7.2.1

Overcurrent protection

The brake chopper hardware is monitored with regard to overcurrent (short circuit or earth fault).

• If monitoring responds:

• The brake chopper is switched off immediately.
• The "Fault" response is activated.
• The "Brake transistor: overcurrent" error message is entered into the logbook of the

controller.

Tip!
In addition to the overcurrent protection the controller is provided with two further

monitoring functions for the braking operation, which are also activated if no brake resistor

is connected at all (testing mode for checking the parameterisation):

Ixt utilisation - brake transistor

( 269)

I2t utilisation - brake resistor

( 270)

Note!

The monitoring with regard to overcurrent can only be triggered if a braking current is

actually available. It is not possible to carry out a test in idle state (without connected

brake resistor).

Note!

The error can only be acknowledged after 2 seconds at the earliest to resume the braking

operation.

Advertising
This manual is related to the following products: