3 i2t utilisation - brake resistor, I2t utilisation - brake resistor, I2t utilisation – Lenze 9400 User Manual

Page 270: Brake resistor, 7braking operation

Advertising
background image

7

Braking operation

7.2

Monitoring

270

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.2.3

I2t utilisation - brake resistor

The controller is provided with a monitoring function of the I

2

t utilisation of the brake resistor

which is proportional to the converted braking power.

[7-2]

Signal flow - I2t utilisation - brake resistor

• The monitoring function is based on the mathematical model which calculates the braking

current from the current DC-bus voltage and the brake resistance parameterised in

C00129

.

• Hence, monitoring can be activated although no brake resistor is connected and can

therefore also be used for a testing mode to check the parameterisation.

• During the calculation, the thermal utilisation of the brake resistor on the basis of the following

parameters is taken into consideration:

• Resistance value (

C00129

)

• Continuous power (

C00130

)

• Thermal capacity (

C00131

)

C00138

displays the calculated utilisation of the brake resistor in [%].

• A 100 % utilisation corresponds to the continuous power of the brake resistor which results

at the maximum permissible temperature limit of the brake resistor.

• The calculated utilisation is provided as oscilloscope signal Common.dnI2tBrakeResistor to

check the braking operation while the system is running
(scaling: 2

30

≡ 100 %).

• If the utilisation exceeds the advance warning threshold set in

C00572

, "Brake resistor: I2t >

C00572" is entered in the logbook and the response set in

C00571

(default setting: "Warning")

is activated.

Note!

If the DC-bus voltage exceeds the overvoltage threshold due to a too high braking

energy, the monitoring function for overvoltage in the DC bus responds.

DC bus

overvoltage

( 272)

Note!

The braking operation will never be switched off by this monitoring function.

I2t

C00138

C00129

T

= 0

Off

T

= 1

On

100 %

C00572

C00571

C00574

C00129
C00130
C00131

Logbook entry "

"

Brake resistor: I2t > C00572

Logbook entry "

"

Brake resistor: I2t overload

U

DC_act

Temperature model

I

=

Br

I

Br