7.2.2

Ixt utilisation - brake transistor

The controller is provided with a monitoring function for the Ixt utilisation of the internal brake

transistor.

[7-1]

Signal flow of Ixt utilisation - brake chopper

• Monitoring is based on a mathematical model which calculates the braking current from the

current DC-bus voltage and the brake resistance parameterised.

• Hence, monitoring can be activated although no brake resistor is connected and can

therefore also be used for a testing mode to check the parameterisation.

• During the calculation the thermal utilisation of the brake transistor is taken into consideration

by the use of an accordingly adapted time constant.

• In

C00133

it can be selected whether the minimum brake resistance (display in

C00134

) which

depends on the network setting in

C00173

) or the brake resistor value parameterised in

C00129

is to be used as a reference for calculating the utilisation.

C00137

displays the calculated utilisation of the brake transistor in [%].

• A 100 % utilisation corresponds to the continuous braking power which is provided by the

integrated brake chopper at a DC-bus voltage of 790 V (or 390 V at a mains voltage of 230 V).

• The maximum braking power (assuming that the utilisation starts at 0 %) can be provided for

a time period depending on the device.

• The calculated utilisation is provided as oscilloscope signal Common.dnIxtBrakeChopper to

check the braking operation while the system is running
(scaling: 2

30

≡ 100 %).

• If the utilisation exceeds the advance warning threshold set in

C00570

, "Brake chopper: Ixt >

C00570" is entered in the logbook and the response set in

C00569

(default setting: "Warning")

is activated.

• When the utilisation reaches the limit value (100 %):

• The activation of the brake chopper is reset to the permanently permissible mark-to space

ratio (taking the parameterised brake resistance into consideration). (The brake chopper is

activated with 4 kHz, which means that it can be switched on/off at minimum intervals of

250 μs.)

• The response set in

C00573

(default setting: "No response") is activated with the

corresponding effects on the state machine and the inverter.

Note!

The braking operation will never be switched off by this monitoring function.

Ixt

C00137

1

0

C00134

C00129

C00133

T

= 0

Off

T

= 1

On

100 %

C00570

C00569

C00573

Logbook entry "Brake chopper: Ixt > C00570"

Logbook entry "

"

Brake transistor: Ixt overload

U

DC_act

U

DC_act

I

=

Br

I

=

Br

I

Br

= f(duty cycle, R )