Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

275

8

I/O terminals

8.2

Analog inputs

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.2.2

Parameter setting

Short overview of parameters for the analog inputs:

8.2.3

Reconfiguring analog input 1 into current input

By means of the following two steps, analog input 1 can be reconfigured into a current input:

1. Bridge the terminals A1R and A1- at terminal strip X3 by means of wiring.
2. Select the corresponding current loop under

C00034

.

Tip!
Like this you can implement a 4 ...20 mA current loop, e.g. for speed setpoint selection.

Open-circuit monitoring
Under

C00598

you can set an error response to open circuit for the 4 ...20 mA current loop.

Parameter

Info

C00034

Config. analog input 1

C00598

Resp. to open circuit AIN1

C02730/1

Analog input 1: Gain

C02730/2

Analog input 2: Gain

C02731/1

Analog input 1: Offset

C02731/2

Analog input 2: Offset

C02732/1

Analog input 1: Dead band

C02732/2

Analog input 2: Dead band

C02800/1

Analog input 1: Input signal (-16384 ≡ -100 %, 16383 ≡ 100 %)

C02800/2

Analog input 2: Input signal (-16384 ≡ -100 %, 16383 ≡ 100 %)

Greyed out = display parameter