11

Basic drive functions

11.5

Manual job, encoderless

410

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.5.2.1

Requirements

• Check and, if necessary, adjust the basic parameterisation:

• Optimisation of the current controller in the case of non-Lenze motors or motors that are not

included in the »Engineer« motor catalogue.

Optimising the current controller

( 178)

• Parameterisation of motor monitoring corresponding to the existing motor with the

monitoring response "Fault".

Motor monitoring (I

2

xt)

( 215)

• This function is especially important for monitoring the permissible r.m.s. current load on

motors at f

d

= 0 Hz.

• Activation of maximum current monitoring with the monitoring response "Fault" in the case

of non-Lenze motors or motor that are not included in the »Engineer« motor catalogue.

Maximum current monitoring

( 230)

• Activation of motor temperature monitoring via PTC and/or KTY.

Motor temperature

monitoring

( 222)

• The controller inhibit is active.
• The controller is in the "Controller not ready" state

Device states

( 97)

.

• The basic function "Manual jog (OL)" is part of the active application; see

Internal interfaces

| "LS_ManualJogOpenLoop" system block

( 414)

.

• No other basic function is active.

11.5.2.2

Activation

In order to request the control via the basic function, the MOL_bEnable enable input in the

application must be set to TRUE or

C02770/1

to "1".

• If no other basic function is active, a changeover to the function state "Manual jog, encoderless

active" takes place and controlled traversing can be carried out by means of the control inputs

or by writing values into

C02770/2...5

.

• A successful changeover to the function state"Manual jog, encoderless active" is indicated by a

TRUE signal at the status output MOL_bEnabled.