Heatsink: overtemperature [0x00770001, Motor: temperature > c00121 [0x00770002, Motor: overtemperature [0x00770003 – Lenze 9400 User Manual

Page 642: Cpu: temperature > c00126 [0x00770008, 0x00770008, 0x00770001, 0x00770003, 0x00770002, 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

642

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Heatsink: Overtemperature [0x00770001]

Motor: Temperature > C00121 [0x00770002]

Motor: Overtemperature [0x00770003]

CPU: Temperature > C00126 [0x00770008]

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Heatsink temperature higher than fixed temperature

limit (90 °C).

• Ambient controller temperature too high.

• Dirty fan or ventilation slots.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

2

Response (Lenze setting printed in bold)

Setting:

C00584

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Motor temperature higher than variable temperature

limit (

C00121

).

• Motor too hot due to impermissibly high currents or

frequent and too long acceleration processes.

• No PTC connected.

• Value set under

C00121

is too low.

• Check drive dimensioning.

• Connect PTC or switch off monitoring (

C00584

="0").

• Set a higher value in

C00121

.

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

3

Response (Lenze setting printed in bold)

Setting:

C00583

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Motor temperature higher than fixed temperature limit

(150 °C).

• Motor too hot due to impermissibly high currents or

frequent and too long acceleration processes.

• No PTC connected.

• Check drive dimensioning.

• Connect PTC or switch off monitoring (

C00583

="0").

Module ID (decimal)

Error ID (decimal)

119: Temperature monitoring

8

Response (Lenze setting printed in bold)

Setting:

C00589

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CPU temperature higher than variable temperature limit

(

C00126

).

• Ambient controller temperature too high.

• Dirty fan or ventilation slots.

• Value set under C00126 is too low.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

• Set a higher value in

C00126

.