Publication 1757-IN500A-EN-P - September 2002

4-20 ProcessLogix Server Upgrade Procedures

Exporting the R400.0 ProcessLogix Server Database

If you have a Redundant Server pair, perform these steps on SERVERA only.

1. Logon to the system as ps_user.

2. Enter this command:


>cmd<


and click OK to open the DOS window.

3. At the DOS prompt, enter the following command:


>hscserver /unload /y<


and press <Enter>.

4. Enter the following command:

xcopy C:\Honeywell\server\data\*.* C:\Data\server\backup /E

and press <Enter>.

Hardware definition
files

If you want to use existing hardware definition (hdwbld)
files to build printers, you must change the CYRILLIC
keyword to LANGUAGE=CYRILLIC.

Alarms and
messages

Resolve any alarms before starting the upgrade. Alarms
and messages currently in the system cannot be copied
across for the upgrade.

Handover notes

Handover notes are lost during the upgrade. Handover
notes in the system cannot be copied for the upgrade.

Table 4.E Upgrading an R400.0 Server Considerations

Item

Pre-upgrade Requirement

Post-upgrade

ATTENTION

!

Before exporting the ProcessLogix Server Database, you
must exit all ProcessLogix applications and stop all
ProcessLogix services. Refer to Stopping ProcessLogix
Applications and Services on page 8-1.

If you have redundant servers, you must complete this
procedure on the SERVERB node first. Then complete
the entire procedure again for the SERVERA node.