Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 161

Publication 1757-IN500A-EN-P - September 2002
Additional Redundant Server Procedures 6-5
1. Click Start
⇒
Programs
⇒
ProcessLogix Server
⇒
Start-Stop
ProcessLogix Server to call up the ProcessLogix Server dialog box.
a. With the Full Mode version of the dialog box active, click the
Database Only option.
b. Click Yes to confirm the action and wait for the Server to change its
state.
c. Close the ProcessLogix Server dialog box.
2. Click Start
⇒
Programs
⇒
ProcessLogix Server
⇒
Setup.
3. At the Welcome window, click Next.
4. Check the Change software license checkbox and click Next.
5. Enter the new System and Authorization numbers and click Next.
6. Click Next to confirm.
7. If the license includes a new database size, click Yes in the Rebuild
Database dialog box.
8. When completed, uncheck the Start ProcessLogix Server checkbox and
click OK.
TIP
To display the “Full Mode” version of the ProcessLogix
Server dialog box, click the icon on the left of the title bar
and click Advanced
⇒
Full Mode.
A checkmark will now appear in front of the Full Mode
selection to show that it is active.