Publication 1757-IN500A-EN-P - September 2002

Firmware Maintenance Procedures 7-13

6. To load the personality image to a 1757-FIM, locate the Fimrex.nvs

personality (rex) file. See Table 7.A on page 7-5.

This example illustrates loading the personality image to a 1757-PLX52
for CEE-50ms.

7. When the correct file appears in the list box, select it so that it appears in

the File Name entry field.

8. Click Open to start the firmware load and click Yes to confirm the

action.

9. Wait for the load to complete and the 1757-PLX52, TC-MUX021, or

1757-FIM module to reboot to its NODB status as shown in the
module LED display. The Status field in the lower portion of the
Network Tools window tracks the load progress.

10. Click OK to acknowledge the load completion with no errors.

11. Confirm that the LED display on the 1757-PLX52, TC-MUX021, or

1757-FIM module shows NODB.

12. Repeat the procedures in the Sections entitled Loading boot image and

Loading personality image for other 1757-PLX52, TC-MUX021, or
1757-FIM modules in your network, as required. Be sure to update the
partner 1757-PLX52 module in an RCP system configuration.

13. Click Network Tools

Exit to close the application. Continue with

other firmware upgrades as applicable in the next Section or return to
upgrade or installation procedures as applicable.