Publication 1757-IN500A-EN-P - September 2002

Performance and Capacity Specifications 11-7

Control Builder Considerations

Viewing the expanded Monitoring Tab Tree View of the same 1757-PLX52
Controller loaded with more than 500 total CMs, SCMs and IOMs from more
than one CB client simultaneously, will severely affect the performance of the
1757-PLX52 Controller’s communication capability, both to the Server and
Peer-to-Peer.

Using multiple CB clients to load to multiple controllers simultaneously
actually increases the overall load time. Do not employ this technique as a way
to save time in loading a controller with contents.

Database operations (load, delete, upload, update, etc.) initiated from a CB
client will affect the performance of applications that run on the backup
Server. Remote CB clients will also be affected by these operations. For
instance, a CB client will experience reduced performance if another CB client
is also connected to the same Server and has requested a large database
operation.

Control Builder supports multi-user functionality, however, it should be noted
that there are some operations that are restricted. Specifically, if a load is
carried out at the same time as database modifications are in progress
(including import, copy, delete), then these operations may fail, displaying
related error messages. Examples of such errors include:

Typical Display Call Up Time with 100 Parameters on a Single
Station/Server

(Call up time is dependent on display complexity; this excludes
the first initial call up.)

< 2 sec

Maximum Number of Stations Connected to one Server

20

Maximum Number of Concurrent Users Connected to one Server.

See Table 11.G Server communication NetBIOS session capacity
on page 11-9.

Unlimited for Windows 2000
Sever based system

Table 11.E Multi-user CB/FLM Operational Limits

Multi-user CB/FLM Limits

Maximum CB Clients connected to single Server

4

Remote Access Service (RAS) support for Multi-User CB

Not Supported

Dial-up Networking support for Multi-User CB

Not Supported

Minimum continuously available Network Bandwidth required for each
multi-user CB Client.

128KB

Maximum Fieldbus Library Manager Clients connected to a single server

1