ProcessLogix Server Upgrade Procedures 4-35

Checking Control Builder Operation and Logging On

Use the following general procedure to log on and check Control Builder
operation on a ProcessLogix Server.

Changing the default Operator's password

In previous releases of ProcessLogix it was not necessary to change the default
mngr operator's password to use it. As a security precaution it is now necessary
to change the password before you can log in as the mngr operator. To change
the password, do the following:

1. Open Station.

2. Click the Oper field in the lower right corner of the display.

3. Enter >mngr< in the Station logon prompt and click OK.

4. Click Configure

Operator

Operators.

5. Click the mngr Operator ID.

6. Click Change Password.

7. Enter the New Password, Confirm the New Password and click OK.

The message Password accepted should appear in the message zone.
If it does not repeat steps 7 and 8.

Only systems using operator based security and Control Builder are
affected by this change. The mngr operator account is different than the
Windows mngr user account. Navigate in Knowledge Builder to
Administration and Startup Guide for more information before changing
the password of the Windows mngr user account.

8. Click Start

Programs

ProcessLogix Engineering Tools

Control Builder.

9. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.
b. Enter the appropriate Password.
c. Enter the appropriate Server name in the Server Name field.
d. Choose Classic Server Security in the Domain Name drop down box.

10. Click OK.