I/o performance and capacity specifications, I/o performance and capacity specifications -21 – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual

Page 261

Advertising
background image

Publication 1757-IN500A-EN-P - September 2002

Performance and Capacity Specifications 11-21

I/O Performance and
Capacity Specifications

Every I/O device presents a load on the 1757-PLX52 system performance by
utilizing I/O network bandwidth and 1757-PLX52 memory and CPU
resources.

Many of these constraints are measured in I/O Units, which is a generic
loading definition used to normalize the load among the many different I/O
devices and families supported.

Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for the I/O
unit load assigned to various devices and modules. By following these
configuration constraints, you can prevent the 1757-PLX52 from being
overloaded and increase the ability for the 1757-PLX52 to operate correctly..

Table 11.R I/O Unit Load Constraints

I/O Device or Module

I/O Units

1 1756/1757 chassis mounted I/O Module

1

1 1794 FLEX I/O or 1797 FLEX EX rail mounted I/O Module 1

1 1757-SIM FTA

4

1 1788-CN2FF, Foundation Fieldbus Linking Device

1

1 1757-FIM, Fieldbus Interface Module

3

1 DHRIO Module

1

1 SST-PFB-CLX Profibus Module

2 (for 64 Unit/CPM Limit)
6 (for 24 Unit/CNB Limit)

1 1756-DNB, DeviceNet Interface Module

1

Table 11.S I/O Module Capacity

I/O Module and Fieldbus Capacity

50 ms CEE

5 ms CEE

Maximum Number of I/O Units per 1757-PLX52
Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for I/O unit definitions.

64

12

(local 1757/1756 I/O only)

Maximum Number of Remote I/O Chassis + 1757-FIM-Only Chassis+Remote Mixed
Chassis + 1794/1797-ACNR15s (combined) per 1757-PLX52.

8

0

(local 1757/1756 I/O only)

Maximum Number of I/O units per Downlink 1756-CNB
Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for I/O unit definitions.

64 scheduled

24 unscheduled

0

(local 1757/1756 I/O only)

Maximum number of Downlink 1756-CNB’s per Controller Chassis

4

0
(local I/O only)

Maximum number of DHRIO modules per 1757-PLX52

2

2 (local chassis only)

Serial Interface Module: (TC-MUX021) related only

50ms CEE

5ms CEE

Maximum Number of Serial Interface Modules per 1757-PLX52

3

1

Maximum Number of FTA assemblies per Serial Interface Module (TC-MUX021)

• Each FTA connected counts as 4 I/O units in the 64 I/O units per 1757-PLX52 and

the 24 I/O units per 1756-CNB calculation above.

2

2

1788-CN2FF related only:

50ms CEE

5ms CEE