Transferring r320.0 data to the r500.1 server, Transferring r320.0 data to the r500.1 server -11 – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual

Page 99

Advertising
background image

Publication 1757-IN500A-EN-P - September 2002

ProcessLogix Server Upgrade Procedures 4-11

b. On SERVERA, enter this command:


>NET USE T: \\PLX1A\C$ /user:ps_user<

(where PLX1A is the name of the R500.1 Primary Server)


and press <Enter>.

c. Open Windows Explorer on each R320.0 Server and confirm that

the T: drive exists.

Transferring R320.0 Data to the R500.1 Server

1. On the R320.0 Server(s), click Start

Run.

2. Enter this command:


>cmd<


and click OK to open the DOS window.

3. If you have a non-redundant server:

a. Enter this command:


>xcopy C:\Data\*.* T:\R320Data\ /E<


and press <Enter>.

b. If necessary, enter >D< to specify that R320Data is a directory.
c. Wait until the C:\ prompt appears and close the DOS window.

4. If you have a redundant server pair: