Upgrading Hardware Component Firmware

1. Refer to Loading 1757-PLX52, TC-MUX021, or 1757-FIM Boot and

Personality Images on page 7-9 to upgrade the 1757-PLX52 boot and
personality images to the current release level.

2. After upgrading the 1757-PLX52, refer to Upgrading Hardware

Component Firmware on page 7-4 to check if other hardware
components require upgrades.

Checking Control Builder Operation and Logging On

Use the following general procedure to log on and check Control Builder
operation on a ProcessLogix Server.

Changing the default Operator's password

In previous releases of ProcessLogix it was not necessary to change the default
mngr operator's password to use it. As a security precaution it is now necessary
to change the password before you can log in as the mngr operator. To change
the password, do the following:

1. Open Station.

2. Click the Oper field in the lower right corner of the display

3. Enter >mngr< in the Station logon prompt and click OK.

4. Click Configure

Operator

Operators.

5. Click the mngr Operator ID.

6. Click Change Password.

IMPORTANT

Stop! It is essential that you check the firmware revision
levels for ALL ProcessLogix hardware components after a
ProcessLogix software installation.

Do not proceed until you have upgraded the firmware.