5-14 ProcessLogix Client Installation and Upgrade Procedures

Installing ProcessLogix
R500.1 Client Software

Use the following procedure to install the ProcessLogix R500.1 Client
software.

1. Logon to the system as ps_user.

2. Close all running applications.

3. Insert the ProcessLogix R500.1 Base Software CD into the CD-ROM

drive.

9.

Quick Builder

10.

VBScript Documentation

11.

Control Component Library (Engineering

Workstation Only)

12.

Shape Library 400.0

13.

PsAxCtl Document EXE (Engineering Workstation

Only)

14.

Display Builder 320.2

15.

PSC Engineering Tools (Engineering Workstation

Only)

16.

Knowledge Builder

17.

PLX System Installer

18.

ProcessLogix - Remove this last

Table 5.J Removal of Selected R400.0 Components

Order

Component

IMPORTANT

If you plan to use Microsoft Excel Data Exchange,
Microsoft Excel must be installed before installing
ProcessLogix.

Prior to the ProcessLogix installation, it is mandatory that
the Excel macro security level is set to Medium. To change
the security level for macro virus protection in Excel:

1. On the Tools menu, click Macro, then click Security.
2. Click the Security Level tab, select Medium and click OK.
3. Close Excel.

IMPORTANT

Be sure to logon as ps_user. If you don’t have a user
ps_user account, you must create one at this time. Refer
to Creating the ProcessLogix User Accounts on page 2-41
.