7-18 Firmware Maintenance Procedures

Updating Firmware in ABRIO

Follow this procedure for updating the firmware in the 1757-ABRIO module.

1. Logon the Server as ps_user.

2. Insert the ProcessLogix R500.1 Supplemental CD.

3. Click Start

Run.

4. Browse to: >CDROM Drive Letter<:\ABRIO Control Flash\setup.exe

5. Click OK.

6. At the Welcome to ControlFLASH Setup window, click Next.

7. Click Yes to accept the License Agreement.

8. Click Next to accept the default location.

9. Uncheck the Yes, I want to view the ControlFLASH readme file.

10. Check Yes, I want to launch ControlFLASH and click Finish.

11. At the Welcome to ControlFLASH window, click Next.

12. Click 1757-ABRIO and click Next.

13. Expand RSLinx Tree window to the location of the 1757-ABRIO

module you wish to flash.

14. Select the module icon and click OK.

15. Confirm that the update revision is 1.1 and click Next.

16. At the Summary window, click Finish.

17. Click Yes to confirm the flash.

18. Click OK.

If this update is successful, the Update Status window will display the
following message in green: Update Complete.. Please verify this new
firmware update before using the target device in its intended
application.

19. Click OK and then click Cancel at the Welcome to ControlFLASH

Setup window.

20. Click Yes to end the configuration session.