Publication 1757-IN500A-EN-P - September 2002

Operating System Installation Procedures 2-23

d. Click Next.

13. Choose the Custom settings option and click Next.

14. At the Networking Components window, select Internet Protocol

(TCP/IP) and click Properties.

15. In the Internet Protocol (TCP/IP) Properties window.

a. Click the Use the following IP address option.
b. Enter the appropriate IP address information.

The following Private Networking IP Address scheme can be utilized
for the system to operate:

c. Enter the Subnet Mask 255.255.255.0.
d. Enter a default gateway if necessary.

ATTENTION

!

Failure to uncheck the Automatic adjustment for Daylight
Savings Time will cause Redundant Systems to loose
“Sync” when the time is automatically adjusted. Choosing
not to automatically adjust the time allows you to decide
when to make the adjustment (at a time that is not critical
to your process).

TIP

If setup has not found a suitable Network Device, you will
be prompted for installing one. Follow the instructions for
adding a manufacturer supplied driver or add the Microsoft
Loop Back adapter.

Table 2.C Private Networking IP Address scheme

PC Type

Suggested Private Networking IP Address

Client

NIC 1: 192.168.0.x

NIC 2: 192.168.1.x

where x is the Station number +2 (for Station number 2, x=4)