Publication 1757-IN500A-EN-P - September 2002

4-32 ProcessLogix Server Upgrade Procedures

c. Deselect the following Point Names:

All CEEs
All CPMs (only if importing from R320.0)
example_cascade
example_motor
example_pid
example_scm
pidloop

6. Click Import.

Depending on the size of your database, this may take several minutes to
several hours.

7. When completed, close the Import Window (if it did not automatically

close).

8. Close Control Builder.

Restoring the ProcessLogix Server Points Database

Perform the steps below to restore the Server database. For a Redundant
Server Pair, perform these steps on the SERVERA node only.

1. Logon to the system as ps_user.

2. Click Start

Run.

3. Enter this command:

>cmd<

and click OK to open the DOS window.

4. At the DOS prompt, enter the command:

>hscserver /unload /y<

and press <Enter>.

ATTENTION

!

Before restoring the ProcessLogix Server Database, you
must exit all ProcessLogix applications and stop all
ProcessLogix services. Refer to Stopping ProcessLogix
Applications and Services on page 8-1.

If you have redundant servers, you must complete this
procedure on the SERVERB node first. Then complete
the entire procedure again for the SERVERA node.