Publication 1757-IN500A-EN-P - September 2002

8-26 Supplementary Procedures

11. Click Operate

Inactivate

This CEE’s SCMs to inactivate all

assigned SCMs, if applicable.

12. Click Yes in the dialog box to confirm the action.

13. Click Operate

Inactivate

This CEE and its IOMs and CMs to

inactivate the CEE and all assigned IOMs and CMs.

14. Click Yes in the dialog box to confirm the action.

Color of all icons changes to Blue.

15. Select the contents (CMs, SCMs, IOMs) of the CEE folder and click

Edit

Delete.

16. Click Delete Selected object(s) to delete the selected objects.

17. Click the CPM icon, and click Edit

Delete.

18. Click Delete Selected object(s) to delete the non-redundant CPM.

19. In Project tab, click the CEE folder icon.

20. Click Tools

Assign to call up the Controller Assignments dialog

box.

21. Confirm that the check boxes for the selection Show CMs and Show

IOMs are checked.

22. Select the CEE associated with the non-redundant CPM in the Select a

CEE list box.

23. Select all the modules listed in the Assigned Modules list box.

Document the modules you will be unassigning.

24. Click Unassign.

25. Wait for modules to be unassigned and removed from the Assigned

Modules list box.

26. Click Close and return to the Project tab.

27. Click the CPM icon and click Edit

Delete.

28. Click the Delete Selected object(s) button to delete the CPM and its

associated CEE.

29. Close Control Builder.